نمایش منو
Abbreviations used for cable’s designation (Acc to DIN/VDE standard)
A) General
Y : Polyvinyl Chloride (PVC) For Insulation or Sheath
Yw : Heat Resistant Polyvinyl Chloride (PVC) For Insulation or Sheath (90oC or 105oC)
Yf : Improved Flame Retardant & Reduced Smoke Polyvinyl Chloride (PVC)
2Y : Polyethylene (PE) For Insulation or Sheath
2X : Cross-linked Polyethylene (XLPE)
K : Lead cover (LC)
R : Round steel wires (SWA)
B : Steel tape (STA)
AWA : Aluminum wires (used for Armouring)
ATA : Aluminum tapes (used for Armouring)
Gb : Counter open helix tape
(F) : Water blocking tape
H : Flame retardant, Low smoke & Halogen Free (FRLH)
O : Oil resistant outer sheath (Hydrocarbon resistant) Acc to VDE 0472-803
Q : Steel Braid Wire Armour
vzn : Tinned Copper
B) Power and Control Cables
N : Copper conductor (CU) (DIN VDE Standard)
NA : Aluminum conductor (AL) (DIN VDE Standard)
-O : Cable core hasn›t green-yellow (Earth) wire
-J : Cable core has green-yellow (Earth) wire
S : Copper tape in common screen (CTSC)
C : Concentric copper wires in common screen (CWSC)
S : Screen of copper in common (SC) ; for MV
SE : Screen of copper over each individual core (SC) ; for MV
C) Instrument & Telephone & Signaling Cables
A- : Outdoor telecommunication cables
AJ- : Outdoor telecommunication cables with induction protection Generally used for railway signaling cables SLg : Signalling cables
D : Concentric copper wires (Railway-Signal cables)
D : Spiral tinned copper wires (Equipment & Electronics cables)
02YS : FPE with skin layer of PE
J- : Indoor telephone cables
JE- : Industrial electronic cables
S- : Switchboard cables
RE- : Instrumentation cables (stranded conductor)
RD- : Instrumentation Rehnomatic cables
Li : Equipment wires and cables (fexible conductor) Generally used for special and sensitive electronic usage
(St) : Static screen ; Al.foil or Copper tape (OSC : Overall screen) Consist of Aluminum polyester tape with a drain wire.
(L) : Aluminum co-polymer (OSC : Overall screen) usually applied longitudinall
F : Jelly-Filled compound
PiMF/TiMF : Pair/Triple in metallic foil (ISC : Individual screen) Each element has individual screen
PiMFY/TiMFY : Pair/Triple in metallic foil + Pair/Triple Jacket Each element has individual screen and jacket